Annual Backflow Testing in Lady Lake, FL

Your water utility mailed a notice. It names a device, a serial number and a due date. That letter is the start of annual backflow testing, and Grizzly Backflow & Plumbing connects you with a local tester in Lady Lake, FL who can handle it.

The tester closes the downstream shutoff, hooks a differential pressure gauge to the test cocks and reads each check valve in turn. On a double check, each check has to hold at least 1.0 psid. On an RPZ, the relief valve has to open at no less than 2.0 psid. The numbers go on the report exactly as read.

Most residential tests take about half an hour, and your water is off for part of it. Commercial assemblies take longer, especially 4 inch and larger devices.

If the device passes, the report gets filed. If it fails, you get the reason in plain words and the options: repair, rebuild or replace.

Backflow prevention only works when the device is checked on schedule. Call Grizzly Backflow & Plumbing at (833) 990-5874 to book your test in Lady Lake, FL.

How it works

Four steps to backflow testing in Lady Lake, FL

  1. 01

    Grab your notice

    Have the utility letter handy. It lists the device, serial number and due date.

  2. 02

    Talk it through

    Call (833) 990-5874. We go over the device type and the price before anything is booked.

  3. 03

    Test day

    A certified tester reads each check and the relief valve on a calibrated gauge.

  4. 04

    Report filed

    The report goes to your water utility, and you keep a copy for your records.

Coverage

Backflow Testing Services Across Lady Lake, FL

Backflow testing for the neighborhoods and ZIP codes around Lady Lake, FL.

Neighborhoods we cover for backflow testing

  • Lady Lake
  • The Villages

ZIP codes we serve

32159

Backflow testing FAQs

Questions about backflow testing

Questions we hear most often about Annual Backflow Testing in Lady Lake, FL.

Talk to a person
Why is water dripping from my RPZ relief valve?
A steady drip usually means debris is holding the first check open or the relief valve diaphragm is worn. A cleaning or a rebuild kit fixes most cases.
Can a backflow preventer freeze?
Yes. Trapped water expands and can crack the bronze body or blow out the bonnet. Insulated enclosures, heat cable or draining the device for winter prevent it.
What is a cross-connection?
Any point where drinking water piping can come into contact with a non-potable source. Common examples are a hose in a bucket, a boiler fill line and an irrigation system.
How much does backflow testing cost in Lady Lake, FL?
Pricing depends on device type, size and the local market. Call (833) 990-5874 for current pricing on backflow testing in Lady Lake, FL.
Is fire sprinkler backflow testing different?
Yes. Along with the standard check valve test, NFPA 25 calls for an annual forward flow test on fire line backflow assemblies. Results often go to both the water utility and the fire authority.